MONSANTO CO -- ASKAREL CAT#:M-508A-1 & M-508A-2,(PCBS),AROCLOR SERIES(SUPP) -- 5910-00-197-4068
===================== Product Identification =====================
Product ID:ASKAREL CAT#:M-508A-1 & M-508A-2,(PCBS),AROCLOR SERIES(SUPP)
MSDS Date:09/01/1993
FSC:5910
NIIN:00-197-4068
MSDS Number: BWMPP
=== Responsible Party ===
Company Name:MONSANTO CO
Address:800 N LINDBERGH BLVD
City:ST LOUIS
State:MO
ZIP:63167
Country:US
Info Phone Num:314-694-6661
Emergency Phone Num:314-694-6661, CHEMTREC 800-424-9300
CAGE:76541
=== Contractor Identification ===
Company Name:ACCUSTANDARD INC
Address:125 MARKET ST
Box:City:NEW HAVEN
State:CT
ZIP:06513
Country:US
Phone:800-442-5290
CAGE:0U4A8
Company Name:MONSANTO COMPANY
Address:800 N LINDBERGH BLVD
Box:City:SAINT LOUIS
State:MO
ZIP:63167
Country:US
Phone:314-694-6661 OR 800-332-3111
CAGE:76541
============= Composition/Information on Ingredients =============
Ingred Name:POLYCHLORINATED BIPHENYLS (PCBS) (SARA III)
CAS:1336-36-3
RTECS #:TQ1350000
Other REC Limits:NONE RECOMMENDED
ACGIH TLV:1 MG/M3; 9394
EPA Rpt Qty:1 LB
DOT Rpt Qty:1 LB
Ingred Name:CHLORODIPHENYL;42% CHLORINE (AROCHLOR 1242) (SARA III)
CAS:53469-21-9
RTECS #:TQ1356000
Other REC Limits:NONE RECOMMENDED
OSHA PEL:S, 1 MG/M3
ACGIH TLV:S, 1MG/M3; 9394
EPA Rpt Qty:1 LB
DOT Rpt Qty:1 LB
Ingred Name:AROCLOR 1248 (SARA III)
CAS:12672-29-6
RTECS #:TQ1358000
Other REC Limits:NONE RECOMMENDED
EPA Rpt Qty:1 LB
DOT Rpt Qty:1 LB
Ingred Name:CHLORODIPHENYL;54% CHLORINE (AROCHLOR 1254) (SARA III)
CAS:11097-69-1
RTECS #:TQ1360000
Other REC Limits:NONE RECOMMENDED
OSHA PEL:S, 0.5 MG/M3
ACGIH TLV:S, 0.5MG/M3; 9394
EPA Rpt Qty:1 LB
DOT Rpt Qty:1 LB
Ingred Name:AROCLOR 1260 (SARA III)
CAS:11096-82-5
RTECS #:TQ1362000
Other REC Limits:NONE RECOMMENDED
EPA Rpt Qty:1 LB
DOT Rpt Qty:1 LB
Ingred Name:AROCLOR 1221, 1232 (SARA III)
CAS:1336-36-3
RTECS #:TQ1350000
Other REC Limits:NONE RECOMMENDED
ACGIH TLV:1 MG/M3; 9394
EPA Rpt Qty:1 LB
DOT Rpt Qty:1 LB
Ingred Name:AROCLOR 1016 (SARA III)
CAS:12674-11-2
RTECS #:TQ1351000
Other REC Limits:NONE RECOMMENDED
EPA Rpt Qty:1 LB
DOT Rpt Qty:1 LB
Ingred Name:OTHERS
Other REC Limits:NONE RECOMMENDED
===================== Hazards Identification =====================
Routes of Entry: Inhalation:YES Skin:YES Ingestion:YES
Reports of Carcinogenicity:NTP:YES IARC:YES OSHA:NO
Health Hazards Acute and Chronic:REPEAT/PROLONG CONTACT MAY CAUSE
CHLORACNE IN SOME PEOPLE.SKIN:ABSROBED THRU INTACT SKIN.LOC ACTION
SIMILAR TO COMMON ORG SOLVENTS-REMOVES NATURAL FATS/OILS RESULTING
IN DRYING/CRACKING.EYE:MODERATELY IRRIT.INGEST:SLIGHTLY
TOXIC.INHAL:ANIMAL EXPERIMENTS SHOWED 54% CHLORINATED MATL PRODUCES
MORE LIVER INJURY THAN 42%.
Explanation of Carcinogenicity:PER MSDS:PCBS HAVE BEEN LISTED IN IARC
GROUP 2B & IN NTP.
Effects of Overexposure:CHLORACNE. DRYING & CRACKING SKIN. MODERATELY
EYE IRRITANT. SLIGHTLY TOXIC BY INGEST. LIVER INJURY.
Medical Cond Aggravated by Exposure:A POTENTIAL EXISTS FOR CONTRACTING
OF CHLORACNE IN SOME PEOPLE.
======================= First Aid Measures =======================
First Aid:INGEST:CONSULT PHYSICIAN.DO NOT INDUCE VOMIT OR GIVE ANY OILY
LAXATIVES.SKIN:IF LIQ/SOLID PCBS SPLASHED/SPILLED ON SKIN REMOVE
CONTAMIN CLOTH.WASH SKIN THOROUGHLY W/SOAP/WATER.EYES:IRRIGATE
IMMED W/CO PIOUS QUANT OF RUNNING WTER FOR @LEAST
15MINS.PETROLATUM-BASED OPHTHALMIC OINTMENT MAY BE APPLIED TO
RELIEVE IRRIT EFFECTS.INHAL:REMOVE TO FRESH AIR.IF RASH/RESP IRRIT
PERSIST CALL PHYSICIAN.(SUPPLEM)
===================== Fire Fighting Measures =====================
Flash Point:FIRE-RESISTANT
Extinguishing Media:PCBS ARE FIRE-RESISTANT COMPOUNDS.
Fire Fighting Procedures:STD FIREFIGHTING WEARING APPAREL & SCBA SHOULD
BE WORN WHEN FIGHTING FIRES THAT INVOLVE POSSIBLE EXPO TO CHEM
COMBUST PROD.CLEAN WELL/DECONTAMIN EQMPT AFT USE.
Unusual Fire/Explosion Hazard:IF PCB TRANSFORMER INVOLVED IN
FIRE-RLATED INCIDENT OWENR OF TRANSFORMER MAY BE REQUIRED TO REPORT
INCIDENT.CONSULT/FOLLOW FED/STATE/LOC REGS.
================== Accidental Release Measures ==================
Spill Release Procedures:REMOVE NON-ESSENTIAL PERSONNEL.ADEQUATELY
VENTILATED.CONTAIN SPILL/LEAK.PREVENT MATL ENTERING SEWER
SYS/NAVIGABLE WATERWAYS/STREAMS.REMOVE BY MEANS OF ABSORPTIVE
MATL(SAWDUST,VERMICULITE,DRYSAND,CLAY, DIRT,ETC)OR TRAP/REMOVE BY
PUMPING.USE PPE.
====================== Handling and Storage ======================
Handling and Storage Precautions:NONE SPECIFIED BY MFG.
Other Precautions:FED REGS UNDER TSCA REQUIRE PCBS AND PCB ITEMS TO BE
MARKED.(CHECK REGS FOR DETAILS).AVOID BREATH VAP/MIST.PCB IN ELECT
EQPMT REPORTED TO PROD PCDD & PCDF DURING FIRE SITUATIONS-FROM NON
PCB CMPD-SEE EQMPT MFG.
============= Exposure Controls/Personal Protection =============
Respiratory Protection:USE NIOSH/MSHA APPROVE EQPMT WHEN AIRBORNE EXPO
LIMITS EXCEEDED.FULL FACEPIECE EQMPT RECOMMENDED-CAN REPLACE
FACESHIELD &/OR CHEM SPLASH GOGG.CONSULT RESP MFG FOR
TYP/CONDITIONS.OBSERVED RESP USE LIMI TATIONS.SCBA/SUP AIR
RESP.29CFR1910.134.
Ventilation:PROVIDE VENTI TO CONTROL EXPO LEVELS BELOW AIRBORNE EXO
LIMITS.USE LOC MECHANICAL EXHAU VENTI @SOURCES OF AIR CONTAMIN.
Protective Gloves:APPROP GLOVES(VITON)SEE MFG FOR TYP/OPER
Eye Protection:CHEM SPLASH GOGGLES & FACE SHIELD
Other Protective Equipment:EYEBATHS/SAFT SHOWER.PROT CLOTHING FOR
BARRIER.PROT APRON.
Work Hygienic Practices:LAUNDER CONTAMIN CLOTH BEF REUSE.CLEAN PROT
EQPMT BEF REUSE.WASH THOROUGHLY AFT HANDLING.AVOID BREATH
VAP/MIST,CONTACT.
Supplemental Safety and Health
1016;1221;1232;1242;1248;1254;1260.FLPT:170C 1016;141 150C
1221;152-154C 1232;176-180C 1242;193-196C 1248;NONE
1254/1260.1STAID:DR:LG AMTS INGEST GASTRIC LAVAGE SUGGESTED.HOT
PCBS MAY CAUSE THERMAL BU RNS.IF ELECTR EQMPT ARCS OVER PCBS/OTHER
CHLORINATED HYDROCARBON DIELECTRIC FLUIDS MAY DECOMPOSE TO PRODUCE
HCL-RESP IRR
================== Physical/Chemical Properties ==================
HCC:T6
Vapor Pres:VARIES
Spec Gravity:1.18-1.56 VAR
Viscosity:VARIES
Appearance and Odor:MOBILE OIL/VIS LIQ/STICKY RESIN;APHA COLOR
40/100/150;DEPENDS ON AROCLOR SELECT
================= Stability and Reactivity Data =================
Stability Indicator/Materials to Avoid:YES
NONE SPECIFIED BY MFG.
Stability Condition to Avoid:NONE SPECIFIED BY MFG.
Hazardous Decomposition Products:CO,CO2,HCL,PHENOLICS,ALDEHYDES & OTHER
TOXIC COMBUST PRODS UNDER SEVERE CONDITIONS(EXPO TO FLAME/HOT
SURFACE).
==================== Disposal Considerations ====================
Waste Disposal Methods:ALL WASTES/RESIDUES CONTAINING
PCBS:COLLECT,PLACE IN PROPER CNTNR,MARK,DISPOSE IN MANNER
PRESCRIBED BY EPA REGS(40CFR761)& APPLICABLE STATE/LOC REGS.VAR
FED/STATE/LOC REGS REQUIRE REPORTING PCB SPILLS & CLEANUP
LEVELS.CONSULT ATTORN/OFFICAILS.
Disclaimer (provided with this information by the compiling agencies):
This information is formulated for use by elements of the Department
of Defense. The United States of America in no manner whatsoever,
expressly or implied, warrants this information to be accurate and
disclaims all liability for its use. Any person utilizing this
document should seek competent professional advice to verify and
assume responsibility for the suitability of this information to their
particular situation.